PLUG-IN, IC DIGITAL, Hot INITIATE SWITCH

TNPL Timers

TGC Delay on Make  Relay Timer 10-30 Amps

Timing Mode | Single Shot on Make

Category | Timer with Relay

Series | TNPL

The TNPL Single Shot on Make units meet the needs of customers who require IC digital timing circuits with octal, magnal round or QC bases for plug-in installation. The units are available in SPDT, DPST and DPDT relay forms up to 10 amp with fixed or adjustable time periods.

Timing Mode

Power must be applied to the input voltage terminals continuously. Upon closure of an isolated Normally Open (N.O.) external initiate switch, the load is instantaneously energized and the time delay cycle starts.

Maintained closure or actuation of the external initiate switch during the delay cycle will not affect the time delay period.

When the delay period expires, the timer will reset to its original position and the timer is ready for another cycle.

Cube Relay, 10-30 Amps, Timer with Relay Output
  • CMOS IC digital timing
  • Multi-board construction
  • Relays are sealed
  • Proven circuitry
  • Standard octal (8 pin), magnal (11 pin) plug-ins or 4.75 mm (0.187") blade terminal mountings
  • Factory-fixed or variable timing adjustment
  • Optional remote time adjustment
  • Timing ranges from 0.1 to 1000 seconds standard (special time settings and ranges up to 72 hours also available)
  • ±0.1% Repeat accuracy
  • 100% Operational testing before shipping
Solid State DC Voltage
  • Input Voltage
    VAC: 24, 120, 230, 50/60Hz
    VDC: 12, 24
    Special AC or DC voltages available
  • Operating Voltage
    ±20% of nameplate voltage
  • Relay Contact Ratings
    5 amps DPDT, 10 amps DPDT Optional
  • Repeat Accuracy
    ±0.1% under fixed operating conditions
  • Reset Time
    50 milliseconds
  • Tolerances
    Fixed: ±10%, Optional: ±5%, ±1%
    Variable: +20%, -0%, Optional: +10%, -0%
  • Life Expectancy
    Mechanical: 1 million operations
    Electrical: Up to 100,000 operations at full current load
  • Protection
    Polarity Protection: All DC units have reverse polarity protection
    Transient Strength: 25 joules
  • Temperature Ranges:
    Storage: -40°C to +85°C
    Operating: -25°C to +65°C
  • Housing Material
    High-impact, UL-approved black Lexan