CUBE RELAY, ALTERNATING, TWO OUTPUTS

TGKDDB Timers

TGC Delay on Make  Relay Timer 10-30 Amps

Timing Mode | Repeat Cycle, Off/On

Category | Timer with Relay

Series | TGKDDB

TGKDDB series Cube Relay Repeat Cycle (Dual Adjustable) Off/On timers are a unique combination of solid state timing circuitry with a relay output in a compact cube configuration.

The time delay for both the “Off” cycle and the “On” cycle can be individually adjusted.

These timers offer the many advantages of a relay output and provide the same functional performance as plug-in relay timers, but at a significant cost savings.

Timing Mode

Application of power to the input voltage terminals starts the “Off” delay cycle.

At the end of the “Off” cycle, load 1 is energized, starting the “On” cycle.

At the end of the “On” cycle, load 1 de-energizes and another “Off” cycle starts.

At the end of this “Off” cycle, load 2 is energized for an “On” cycle.

This alternating output action continues until power is removed.

Cube Relay, 10-30 Amps, Timer with Relay Output
  • High current-carrying capacity up to 20 amps
  • 100% Load isolation
  • No leakage in N.O. position
  • No heat sinking required
  • Available in any time delay periods required
  • Digital CMOS timing
  • Transient protected
  • No minimum load required
  • Totally encapsulated for protection from harsh environments
  • 100% Operational testing before shipping
  • RoHS compliance available
Solid State DC Voltage
  • Input Voltage
    VDC: 12, 24-28
    VAC: 24, 120, or 230, 50/60Hz
    Optional: Any in-between AC or DC voltage
  • Time Delay
    Timing Mode: Repeat Cycle Off/On Alternating Outputs
    Type: Digital CMOS
    Time Range: 0.1 second to 24 hours
    Time Adjustments: Variable, with adjustments on timer
  • Repeatability
    ±0.5%
  • Setting Accuracy
    Fixed time period: ±10% of nominal time
    Variable time range: +15% -5% max. time, -10% min. time
  • Reset/Recycle Time
    100 milliseconds
  • Initiate Time
    6 milliseconds or less
  • Relay Life Expectancy
    Mechanical: 20 million operations
    Electrical: 100,000 operations at maximum load
  • Protection
    Polarity Protection: All DC units have reverse polarity protection
    Transient Protection: 18 joules
    Dielectric Strength: 1800V RMS 60Hz
  • Temperature Ranges
    Storage: -40°C to +85°C
    Operating: -25°C to +65°C
  • Physical Data
    Mounting: Surface with one #8 screw
    Connection & Termination: 0.25" quick connects