PLUG-IN RELAY TIMER, IC DIGITAL, INSTANTANEOUS CONTACT
TQCIC Timers
Timing Mode | Delay on Make
Category | Timer with Relay
Series | TQCIC
The TQCIC Delay On Make meets the needs of customers who require IC digital timing circuits with magnal bases for plug-in installation. The units are available in DPDT relay form up to 10 amps with fixed or adjustable time periods, and a 10 amp SPDT instantaneous contact.
Timing Mode
Application of input voltage to the timer starts the time delay. At the end of the delay period, the load is energized. To reset, remove the input voltage to the timer.
- CMOS Integrated Circuit digital timing
- Timing contacts and instantaneous contacts in same timer
- Relays are sealed
- Proven circuitry
- Standard magnal (11 pin) plug-ins
- Fixed or variable time adjustment
- Optional remote time adjustment
- Timing ranges from 0.1to 3600 seconds standard (special time settings and ranges up to 72 hours also available)
- 0.1% Repeat accuracy
- 100% Operational testing before shipping

- Input Voltage
VAC: 24, 120, 230, 50/60Hz
VDC: 24
- Operating Voltage
±20% of nameplate voltage
- Relay Contact Ratings
10 amp DPDT
- Repeat Accuracy
±0.1% under fixed operating conditions
- Reset time
50 milliseconds
- Tolerances
Fixed: ±10%, Optional: ±5%, ±1%
Variable: +20%, -0%, Optional: +10%, -0%
- Life Expectancy
Mechanical: 1 million operations
Electrical: Up to 100,000 operations at full current load
- Protection
Polarity Protection: All DC units have reverse polarity protection
Transient Protection: 25 joules
- Temperature Ranges:
Storage: -40°C to +85°C
Operating: -25°C to +65°C
- Housing Material
High-impact, UL-approved black Lexan