CUBE SOLID STATE, 1 AMP, INPUT VOLTAGE RANGES

THC Timers

TGC Delay on Make  Relay Timer 10-30 Amps

Timing Mode | Delay on Make

Category | Solid State Timer

Series | THC

THC timers are solid state output units with digital timing. The THC comes in a 2" square case.

Ease of installation and hook-up is a primary design benefit. All models with integral time adjustment knob or factory-fixed time require only two connections. They may be wired in-line just like a single pole switch.

Units with external time adjustment have two additional terminals for the resistor or potentiometer.

Note: Available with 277 VAC input rating.

Timing Mode

Application of input voltage to the timer starts the time delay. At the end of the delay period, the load is energized. To reset, remove the input voltage to the timer.

Cube Relay, 10-30 Amps, Timer with Relay Output
  • Digital timing, solid state output
  • 1 Amp current load handling
  • 10 Amps single-cycle surge handling
  • 4 Overlapping AC voltage ranges (from 19 to 277 volts)
  • ±1% Repeat accuracy
  • Virtually unlimited time ranges
  • Factory-fixed or variable-timing adjustment
  • Totally encapsulated for protection from harsh environments
  • O-ring sealed exposed controls
  • Single screw mounting through center mounting hole
  • Standard 6.35mm (0.25") quick connect blade terminals
  • 100% Operational testing before shipping
  • RoHS compliance available
Solid State DC Voltage
  • Input Voltage
    VDC: 12 and 19/48 VDC/VAC
    VAC: 19 to 277 – 4 ranges
  • Repeat Accuracy
    ±0.1% under fixed conditions
  • Timing Ranges
    0.1 sec. to 24 hours (1 sec., 10 sec., 100 sec., and 1000 secs. are standard.)
    Special time ranges available upon request
  • Reset/Recycle Time
    100 milliseconds
  • Tolerances
    Fixed: ±10% of nominal time
    (optional: ±5%, ±1%)
    Variable: -0%, +15%
    Limit: -10% at minimum time
  • Recycle Effect
    None
  • Temperature Ranges
    Storage: -40°C to +85°C
    Operating: -25°C to +65°C
  • Life Expectancy
    No predictable failure if used within operating parameters
  • Protection
    Polarity Protection: All DC units have reverse polarity protection
    Transient Protection: 18 joules
    Dielectric Strength: 1800V RMS 60Hz
  • Power Requirement
    0.25 watts max
  • Weight
    3oz. (85g) maximum
  • Solid State Output
    SPST (N.O.)
  • Load Current
    1 amp continuous, 10 amps single-cycle surge
  • Time Cycle Interrupt (Input Voltage Break)
    Resets timer to original state