DUAL RELAY, TWO OUTPUTS

The TGCD series offers two sequential Delay On Make timing relays in the same package.
Both delay outputs can be factory-fixed or individually adjusted.
Application of power to terminals 2 and 7 starts time period 1. At the end of time period 1, relay 1 transfers (terminal 1 makes to terminal 3) and time period 2 starts.
At the end of time period 2, terminal 8 makes to terminal 6. Reset is via power interrupt at any time during timing.