CUBE RELAY, 10-20 AMPS

TGMLB Timers

TGC Delay on Make  Relay Timer 10-30 Amps

Timing Mode | Delay on Break

Category | Timer with Relay

Series | TGMLB

TGMLB series Cube Relay Delay on Break timers are a unique combination of digital CMOS timing circuitry with a relay output in a compact 2" x 2" configuration.

For users of solid state timers, these units provide the same functional performance as plug-in relay timers, but at significant cost savings.

Key features: Uses a live or hot initiate switch; relay common is internally connected to (+) or hot.

Timing Mode

Input voltage is applied continuously. Upon closure of the normally open live external initiate switch, the load is energized, and remains energized as long as it is closed. When the external initiate switch opens, the time delay is started. At the end of the time delay, the load is de-energized, and the timer is ready for another cycle.

Cube Relay, 10-30 Amps, Timer with Relay Output
  • High current-carrying capacity up to 20 amps, 1.5 HP
  • Transient protected
  • 100% Load isolation
  • No leakage in N.O. position
  • No heat sinking required
  • Available in any time delay period required
  • Uses live initiate switch
  • Pin-for-pin replacement for solid state timers
  • Digital CMOS timing
  • No minimum load required
  • Totally encapsulated for protection from harsh environments
  • 100% Operational testing before shipping
  • RoHS compliance available
Solid State DC Voltage
  • Input Voltage
    VDC: 12, 24-28 or 48
    VAC: 24, 48, 120 or 230, 50/60Hz
    Special AC or DC voltages available
  • Time Delay
    Timing Mode: Delay on Break
    Type: Digital CMOS
    Time Range: 0.1 seconds to 24 hours
    Time Adjustments: Factory-fixed time period; variable, with adjustments on timer, or terminals for external resistor or potentiometer
  • Repeatability
    ±0.5%
  • Setting Accuracy
    Fixed time period: ±10% of nominal time
    Variable time range: +15% -5% max. time, -10% min. time
  • Reset/Recycle Time
    25 milliseconds
  • Initiate Time
    6 milliseconds or less
  • Relay Life Expectancy
    Mechanical: 20 million operations
    Electrical: 100,000 operations
  • Protection
    Polarity Protection: All DC units have reverse polarity protection
    Transient Protection: 18 joules
    Dielectric Strength: 1800V RMS 60Hz
    Control Voltage Isolation: 2500V RMS 60Hz
  • Temperature Ranges:
    Storage: -40°C to +85°C
    Operating: -25°C to +65°C
  • Physical Data
    Mounting: Surface with one #8 or #10 screw
    Connection & Termination: 0.25" quick connects