CURRENT SENSOR with RELAY OUTPUT, 10-20 AMPS

CS Current Sensor

TGC Delay on Make  Relay Timer 10-30 Amps

Timing Mode | Delay After Sense

Category | Current Sensor

Series | CS

The CS is an over or under current sensing control. Toroidal sensing means no break in the power wiring.

The combination of the over current LED, current adjustment, and percentage trip adjustment provides easy and accurate setting.

CS can handle loads up to 20 amps with time delays up to 100 secs.

Sense Mode

When the sensed current increases above or falls below the set point, the time delay will start.

At the end of the delay, the output will be energized.

Cube Relay, 10-30 Amps, Timer with Relay Output
  • Over current and under current sensing
  • Toroidal sensing provides complete isolation between sensed current and control circuit
  • Easy setting of trip point with unique combination of LED indicator, current adjustment and percentage potentiometers.
  • Can switch up to 20 amps (1.5HP)
  • Totally encapsulated for protection from harsh environments
  • Single screw mounting
  • Transient and polarity protected
  • No heat sinking required
  • CMOS time delay
  • 100% Operational testing before shipping
  • RoHS compliance available
Solid State DC Voltage
  • Input Voltage
    +20%/-10%
    VDC: 12 or 24
    VAC: 24, 120, 230, 50/60Hz
  • Time Delay
    Timing Mode: Delay After Sense
    Type: Digital CMOS
    Time Range: 0.1 seconds to 24 hours
    Time Adjustments:
    0.1 second to 10 seconds (adjustable)
    1 to 100 seconds (fixed)
  • Repeatability
    ±0.5%
  • Setting Accuracy
    ±5% or 50 ms., whichever is greater
  • Reset Time
    100 milliseconds
  • Relay Life Expectancy
    Mechanical: Up to 10 million operations
    Electrical: 100,000 operations at max. load
  • Protection
    Polarity Protection: All DC units have reverse polarity protection
    Transient Protection: 18 joules
    Dielectric Strength: 1800V RMS 60Hz
  • Temperature Ranges
    Storage: -40°C to +85°C
    Operating: -25°C to +65°C
  • Sensor
    Toroid–Through hole wiring
    Current Range:
    0.5 to 20 amps
    Frequency: 50/60Hz
    Trip Point Hysteresis: 5% typical
    Trip Point Drift vs Temperature: ±2% typical, ±5% max
    Fixed Setting Accuracy: ±5%